Power Solutions

UPS 2U

Reference UPS-2U

UniFi managed 1.44kVA rackmount uninterruptible power supply with 4 backup and 4 surge outlets, a field replaceable battery, 216Wh, half load (500W) runtime of 8 minutes. Supports Graceful Shutdown for UNVR and UNAS, NUT compatibility for 3-party devices.

  • 14 kg (30.9 lb)Weight
  • Rack mount (2U)Form Factor
  • IP20Weatherproofing

UniFi managed 1.44kVA rackmount uninterruptible power supply with 4 backup outlets, 4 surge outlets, and a field replaceable battery, 216Wh, half load (500W) runtime of 8 minutes. Supports Graceful Shutdown for UNVR and UNAS, and includes NUT compatibility for third-party devices.

Note. For Graceful Shutdown functionality, UniFi OS version 4.4.3 or higher is required.

Deployment

Topology

Technical drawings

What's in the box

Videos

UPS 2U

Key features

1.44 kVA / 1000W Backup Power

Provides reliable battery backup for connected devices during power outages.

8-Minute Backup Runtime

Provides up to 8 minutes of runtime at half load for safe shutdown during outages.

Backup and Surge Outlets

Includes (4) battery-backed and (4) surge-only outlets for flexible power distribution.

Graceful Shutdown and NUT

Monitor power status and enable graceful shutdown for UNVR and UNAS with NUT support for third-party systems.

Specifications

UPS 2U — Specifications
SpecificationValue
Mechanical
Dimensions442.4 x 300 x 87.4 mm (17.4 x 11.8 x 3.4")
Weight14 kg (30.9 lb)
Enclosure MaterialGalvanized steel
Form FactorRack mount (2U)
WeatherproofingIP20
Hardware
ManagementEthernet
Networking Interface(1) 100/10 MbE port for network connection (2) GbE ports for surge in/out
Power(1) OVC II AC in: NEMA 5-15P, 1.8 m (5.9 ft) non-removable power cord (4) Battery backup/surge protection: NEMA 5-15R (4) Surge protection: NEMA 5-15R (Outlets are not individually resettable)
Capacity1,440VA/1,000W
TypeLine interactive
Input Voltage Range89–145V AC
Power Method(1) TN system, 120V AC, 12A Max., 50/60 Hz
Nominal Input Voltage120V AC
Output Voltage120V AC
Frequency RangeAC mode: 50/60 Hz ±5 Hz (Auto sensing) Battery mode: 60 Hz ±1 Hz
AC Voltage Regulation±10% (Battery mode)
Transfer Time6 ms typical; 10 ms max. (Battery mode)
Wave FormSimulated sine wave (Battery mode)
Battery Type(2) Lead Acid 12V, 9Ah
RuntimeFull load: 2.3 min Half load: 8 min
Battery Charging Time6-8 hours recovery to 90% capacity
Overload at On-Line Mode110% 5 min go to fault 120% go to fault immediately
Overload at Battery Mode110% shutdown in 5 sec 120% shutdown immediately
Short Circuit Protection at On-Line ModeBreaker, 250V AC, 15A
Output Short-Circuit CurrentIpeak 348.0A Irms 115.1A
Buttons(1) Power (1) Factory reset
Hardware — LEDs
StatusOff: device not turned on Flashing white: initializing / factory default Steady white: waiting for adoption Steady blue: device adoption and working Flashing blue: battery mode Alternating white/blue: firmware upgrading Rapid flashing blue: locate Steady red: warning Flashing red: low battery
Hardware
Operating Altitude3,000 m (1.9 mi)
Operating EnvironmentPollution Degree 2
Ambient Storage Temperature-20 to 50° C (-4 to 122° F)
Ambient Operating Temperature0 to 40° C (32 to 104° F)
Ambient Operating Humidity0 to 95% noncondensing
NDAA CompliantYes
CertificationsFCC, IC, UL 1778, CSA C22.2 No. 107.3