Power Distribution Pro
Designed to supply power to an entire rack-mounted UniFi system and remotely manage each connection.
Products
Gateways, switches, WiFi, cameras, door access and integrations: every UniFi product line.
View all 203 productsCloud Gateways
WiFi
Physical Security
Build my network
Secure my premises

Power Solutions
Reference UPS-2U-Pro
UniFi-managed 1.92kVA rackmount UPS with pure sine wave output, 8 individually controllable outlets with per-port power monitoring and remote power cycling, a hot-swappable 720Wh battery, and up to 22 minutes of runtime at half load 960W.
UniFi-managed 1.92kVA rackmount UPS with pure sine wave output, 8 individually controllable outlets with per-port power monitoring and remote power cycling, a hot-swappable 720Wh battery, and up to 22 minutes of runtime at half load 960W. Supports Graceful Shutdown for UNVR and UNAS, and NUT compatibility for third-party devices.
Requires:
Note. For Graceful Shutdown functionality, UniFi OS version 4.4.3 or higher is required.







Provides high-capacity battery backup for network and server equipment during power outages.
Provides up to 22 minutes of runtime at half load for safe shutdown during outages.
Includes (8) NEMA 5-20R outlets with battery backup and surge protection.
Replace the battery without powering down connected devices.
Monitor power status and enable graceful shutdown for UNVR and UNAS with NUT support for third-party systems.
| Specification | Value |
|---|---|
| Mechanical | |
| Dimensions | 442.4 x 87.4 x 630 mm (17.4 x 3.4 x 24.8") |
| Weight | 32 kg (70.5 lb) |
| Enclosure Material | Galvanized steel |
| Form Factor | Rack mount (2U) |
| Weatherproofing | IP20 |
| Hardware | |
| Management | Ethernet |
| Networking Interface | (1) 100/10 MbE port for network connection (2) GbE ports for surge in/out |
| Power | (1) OVC II AC in: NEMA 5-20P (8) Battery backup/surge protection: NEMA 5-20R (Outlets are individually resettable) |
| Capacity | 1920VA/1920W |
| Type | Line interactive |
| Input Voltage Range | 89–145V AC |
| Power Method | (1) TN system, 120V AC, 16A Max., 50/60 Hz |
| Nominal Input Voltage | 120V AC |
| Output Voltage | 120V AC |
| Nominal Output Voltage | 120V AC |
| Frequency Range | AC mode: 50/60 Hz ±5 Hz (Auto sensing) Battery mode: 60 Hz ±1 Hz |
| AC Voltage Regulation | ±1.5% (Battery mode) |
| Transfer Time | 6 ms typical; 10 ms max. (Battery mode) |
| Wave Form | Pure sine wave (Battery mode) |
| Battery Type | (1) Lead Acid 72V, 10Ah |
| Runtime | Full load: 9 min Half load: 22 min |
| Battery Charging Time | 8 hours recovery to 90% capacity |
| Overload at On-Line Mode | 103–120% 5 min go to fault 120–150% 10 sec go to fault 150% 1 sec go to fault |
| Overload at Battery Mode | 103–120% 1 min go to fault 120–150% 10 sec go to fault 150% 0.5 sec go to fault |
| Short Circuit Protection at On-Line Mode | Breaker, 250V AC, 20A |
| Emergency Power Off (EPO) | Yes |
| Display | 3.7” touchscreen |
| Buttons | (1) Power (1) Factory reset (1) Circuit breaker |
| Hardware — LEDs | |
| Status | Off: device not turned on Flashing white: initializing / factory default Steady white: waiting for adoption Steady blue: device adoption and working Flashing blue: battery mode Alternating white/blue: firmware upgrading Rapid flashing blue: locate Steady red: warning Flashing red: low battery |
| Ethernet | Yes |
| Hardware | |
| Operating Altitude | 3,000 m (1.9 mi) |
| Operating Environment | Pollution Degree 2 |
| Ambient Storage Temperature | -15 to 50° C (5 to 122° F) |
| Ambient Operating Temperature | 0 to 40° C (32 to 104° F) |
| Ambient Operating Humidity | 0 to 95% noncondensing |
| NDAA Compliant | Yes |
| Certifications | FCC, IC, UL 1778, CSA C22.2 No. 107.3 |
| Software — Application Requirements | |
| Mobile Apps | iOS™: Version 10.36.1 and later Android™: Version 10.39.3 and later |
| UniFi Network | Version 10.5.67 and later |
Request a quote: our team will confirm availability, compatibility and a deployment plan.